Power Planner: How the Math Works
The Power Planner uses plain, cautious rules so nobody ends up short of power in an outage. This page shows every rule, every number and where each number comes from. Back to the Power Planner ›
Energy per day
Every device is turned into watt-hours (Wh) per day: its watts times the hours it runs each day. The Planner fills in typical hours, and you can change them.
Wh per day = watts × hours per day
- Refrigerators and freezers run on and off all day, so their nameplate watts would overstate the energy. The Planner uses the kWh per year from the yellow EnergyGuide label instead (default 600 kWh/yr, which is 1,644 Wh per day): kWh per year × 1,000 ÷ 365.
- Radios draw little while listening and a lot while talking. Each radio gets receive hours and transmit minutes: (receive watts × receive hours) + (transmit watts × transmit minutes ÷ 60). Watts are the maker's current draw × 13.8 V.
- Handheld radios count one full battery charge per day: battery Wh × 1.2, which allows for charger losses.
Battery size
A power station turns its battery's DC power into household AC power, and about 15% is lost in that inverter. So AC devices are divided by 0.85. Devices that can run straight from a 12 V port (CPAP with its DC cord, most radios) skip that loss.
Wh needed per day = (AC Wh per day ÷ 0.85) + DC Wh per day
With solar, the station must hold at least one full day, because a cloudy day or the night has to come out of the battery. With no solar, it must hold the whole outage: Wh needed per day × days.
Days with no sun = station Wh ÷ Wh needed per day
100 W HF radios draw 21 to 23 A on transmit, and most power stations' 12 V car ports stop at about 10 A. When a radio needs more current than the car port gives, the Planner counts it as an AC load through a 13.8 V power supply (with the inverter loss) and tells you so.
Output and surge
Running watts add up because things can run at the same time. Motors (fridge compressors, pumps, furnace blowers, AC units) need a burst of extra starting watts for a second or two. The Planner assumes only one motor starts at a time, which is how you should start them.
Running load = sum of running watts
Peak load = running load + the biggest extra starting watts
A power station fits when its continuous output is at least the running load × 1.2 (20% headroom) and its surge rating is at least the peak load. CPAP machines are also checked against their peak draw (73 W for a ResMed AirSense 11).
Solar panels
A panel's watt rating is what it makes in full, direct sun at a cool temperature. Real panels make less: heat, dust, angle, clouds and charging losses take about a quarter. So the Planner multiplies by 0.75.
Panel watts needed = Wh needed per day ÷ (peak sun hours × 0.75)
Peak sun hours are the hours of full-strength sun a day adds up to. The Planner offers Cloudy / winter = 3, Average = 4 and Sunny = 5. Check your own area on the NREL solar resource maps (linked below), and pick the lower setting for winter.
The Planner never counts more panel than a station can take in (its maximum solar input). If you need more, it says how many days the station will last as it slowly runs down.
Generator size and fuel
Running watts ≥ running load × 1.2
Starting watts ≥ peak load
Fuel comes from each maker's published run times on one tank. Gallons per hour = tank gallons ÷ run hours, at 25% load and at 50% or 100% load where the maker gives it. In between, the Planner draws a straight line. When a maker only gives the 25% figure, the full-load rate is taken as 2.5 times the 25% rate (Honda's EU2200i figures give 2.53).
Your load is the energy your devices need each day spread over the hours you run the generator (default 12 hours a day). Gallons for the outage = gallons per hour × hours per day × days, shown with how many 5-gallon cans that is.
Medical devices and electronics get a note to use an inverter generator, which makes clean power.
- Run it outside only, at least 20 feet from doors, windows and vents (CDC).
- Never in a garage, basement or shed, even with the door open.
- Put a battery carbon monoxide alarm inside the home.
- Let it cool before refueling. Store fuel in approved cans away from the house.
- Never plug a generator into a wall outlet. Connecting to house wiring needs a transfer switch or inlet box installed by an electrician.
How models are picked
For each brand, the Planner shows the smallest model that covers your battery size, running load and peak load. If no model in a brand is big enough, that brand's card says so instead of recommending something that would fail. The models were chosen because they are widely sold and well reviewed; we list both the maker's own store (where we are a partner) and Amazon. As an Amazon Associate we earn from qualifying purchases.
Medical devices: ask your doctor or equipment supplier how long your device runs on battery, keep a backup plan, and tell your power company if someone at home depends on powered medical equipment.
Device numbers
| Device | Running W | Extra starting W | Default use | Source |
|---|---|---|---|---|
| Refrigerator / freezer Energy from your EnergyGuide label (kWh/yr). Running and starting watts from EWEB. |
700 | 2,200 | 600 kWh/yr | Eugene Water & Electric Board, Generator sizing considerations |
| Microwave (1,000 W) | 1,000 | — | 0.25 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Coffee maker | 1,000 | — | 0.25 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Toaster oven | 1,200 | — | 0.25 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Toaster | 850 | — | 0.1 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| LED light bulb | 15 | — | 5 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Flat-screen TV | 120 | — | 3 h/day | Virginia Tech Extension, Estimating Appliance and Home Electronic Energy Use (Feb 2020) |
| AM/FM radio | 100 | — | 3 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Ceiling fan Virginia Tech gives 65 to 175 W. |
75 | — | 8 h/day | Virginia Tech Extension, Estimating Appliance and Home Electronic Energy Use (Feb 2020) |
| Window fan Virginia Tech gives 55 to 250 W. |
100 | — | 8 h/day | Virginia Tech Extension, Estimating Appliance and Home Electronic Energy Use (Feb 2020) |
| Electric blanket (double) | 100 | — | 8 h/day | Virginia Tech Extension, Estimating Appliance and Home Electronic Energy Use (Feb 2020) |
| Space heater | 1,500 | — | 4 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Furnace fan (1/3 HP) Gas furnaces need their blower to run. Most need a transfer switch or inlet box to connect. |
700 | 1,400 | 8 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Window AC (12,000 BTU) | 3,250 | 3,950 | 6 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Dehumidifier | 785 | — | 6 h/day | Virginia Tech Extension, Estimating Appliance and Home Electronic Energy Use (Feb 2020) |
| Phone charger | 20 | — | 2 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Laptop | 60 | — | 4 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Desktop PC + monitor Virginia Tech: computer 120 W + monitor 150 W. |
270 | — | 3 h/day | Virginia Tech Extension, Estimating Appliance and Home Electronic Energy Use (Feb 2020) |
| CPAP, no humidifier ResMed AirSense 10: 0.93 A at 12 V. Run it from a 12 V DC cord to skip inverter losses. |
11 | — | 8 h/day | ResMed battery guide (AirSense 10 at 10 cm H2O, 12 V) |
| CPAP, humidifier on 4 ResMed AirSense 10: 2.30 A at 12 V. |
28 | — | 8 h/day | ResMed battery guide (AirSense 10 at 10 cm H2O, 12 V) |
| CPAP, humidifier on 8 ResMed AirSense 10: 3.66 A at 12 V. |
44 | — | 8 h/day | ResMed battery guide (AirSense 10 at 10 cm H2O, 12 V) |
| Home oxygen concentrator Philips EverFlo average power. Check your own model. |
350 | — | 24 h/day | Philips EverFlo brochure (average power 350 W) |
| Icom IC-7300 (HF, 100 W) 1.25 A receive, 21 A transmit. |
17 receive / 290 transmit | — | 4 h + 15 min | Icom IC-7300 specifications |
| Yaesu FT-891 (HF, 100 W) 2.0 A receive, 23 A transmit. |
28 receive / 317 transmit | — | 4 h + 15 min | Yaesu FT-891 specifications |
| Yaesu FT-991A (HF/VHF/UHF, 100 W) 2.2 A receive, 23 A transmit. |
30 receive / 317 transmit | — | 4 h + 15 min | Yaesu FT-991A specifications |
| Xiegu G90 (HF, 20 W) 0.5 A receive, 8 A transmit (max). |
7 receive / 110 transmit | — | 4 h + 15 min | Xiegu G90 operation manual |
| Icom IC-705 (portable, 10 W) 0.5 A receive, under 3 A transmit. |
7 receive / 41 transmit | — | 4 h + 15 min | Icom IC-705 specifications |
| Kenwood TM-V71A (2 m/70 cm, 50 W) 1.2 A receive, 13 A transmit. |
17 receive / 179 transmit | — | 4 h + 15 min | Kenwood TM-V71A specifications |
| Icom IC-2730A (2 m/70 cm, 50 W) 1.8 A receive, 13 A transmit. |
25 receive / 179 transmit | — | 4 h + 15 min | Icom IC-2730A specifications |
| Yaesu FTM-6000R (2 m/70 cm, 50 W) 0.5 A receive, 10 A transmit. |
7 receive / 138 transmit | — | 4 h + 15 min | Yaesu FTM-6000R operating manual |
| Yaesu FT-65R handheld (charge) | 14.4 Wh per charge | — | 1 charge | Yaesu FT-65R operating manual (SBR-25LI 7.4 V, 1,950 mAh) |
| Baofeng UV-5R handheld (charge) | 13.3 Wh per charge | — | 1 charge | Baofeng UV-5R battery (7.4 V, 1,800 mAh) |
| Midland MXT575 (GMRS, 50 W) Midland publishes 13.8 V but no current draw. Estimated like other 50 W mobiles (about 10 A on transmit). |
7 receive / 138 transmit | — | 4 h + 15 min | Estimate: the maker does not publish this figure. Check your manual and type your own. |
| Midland MXT275 (GMRS, 15 W) Estimated (about 4 A on transmit). Check your manual. |
7 receive / 55 transmit | — | 4 h + 15 min | Estimate: the maker does not publish this figure. Check your manual and type your own. |
| Rocky Talkie 5 Watt Radio (charge) | 13.3 Wh per charge | — | 1 charge | Rocky Talkie 5 Watt Radio battery (7.4 V, 1,800 mAh) |
| Rocky Talkie Mountain Radio (charge) 1,550 mAh; Wh assumes a 3.7 V Li-ion cell. |
5.7 Wh per charge | — | 1 charge | Rocky Talkie Mountain Radio battery (1,550 mAh) |
| Sump pump (1/3 HP) | 800 | 1,300 | 2 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Sump pump (1/2 HP) | 1,050 | 2,200 | 2 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Well pump (1/3 HP) Many well pumps are 240 V. Check yours before picking a generator. |
1,000 | 2,000 | 1 h/day | Eugene Water & Electric Board, Generator sizing considerations |
| Electric water heater 240 V. Generator only, and only through a transfer switch. |
4,500 | — | 2 h/day | Eugene Water & Electric Board, Generator sizing considerations |
Power stations and generators
| Power station | Wh | AC output W | Surge W | Max solar W | 12 V port A |
|---|---|---|---|---|---|
| Jackery Explorer 300 Plus | 288 | 300 | 600 | 100 | 10 |
| Jackery Explorer 1000 v2 | 1,024 | 1,500 | 3,000 | 400 | 10 |
| Jackery Explorer 2000 v2 | 2,042 | 2,200 | 4,400 | 400 | 10 |
| Goal Zero Yeti 700 | 677 | 600 | 1,000 | 200 | 10 |
| Goal Zero Yeti 1500 | 1,505 | 2,000 | 3,600 | 900 | 10 |
| Goal Zero Yeti PRO 4000 | 3,994 | 3,600 | 7,200 | 3,000 | 10 |
| Bluetti Elite 30 V2 | 288 | 600 | 1,500 | — | 10 |
| Bluetti Elite 100 V2 | 1,024 | 1,800 | 3,600 | 1,000 | 8 |
| Bluetti AC180 | 1,152 | 1,800 | 2,700 | 500 | 8 |
| Bluetti Elite 200 V2 Surge counted as 2,600 W: Bluetti lists 3,900 W "power lifting" for heaters and kettles only. | 2,080 | 2,600 | 2,600 | 1,000 | 10 |
| EcoFlow RIVER 3 Max | 572 | 600 | 1,200 | 220 | 10 |
| EcoFlow DELTA 3 Classic | 1,024 | 1,800 | 3,600 | 500 | 10 |
| EcoFlow DELTA 3 Max | 2,048 | 2,400 | 3,400 | — | 10 |
| Anker SOLIX C300 DC No AC outlet: USB-C and 12 V only. | 288 | — | — | 60 | 10 |
| Anker SOLIX C1000 Gen 2 | 1,024 | 2,000 | 3,000 | 600 | 10 |
| Generator | Running W | Starting W | Tank (gal) | Published run time |
|---|---|---|---|---|
| Honda EU2200i Inverter | 1,800 | 2,200 | 0.95 | 8.1 h at 25%; 3.2 h at full load |
| Champion 2500-Watt Ultralight Inverter Inverter | 1,850 | 2,500 | 1.05 | 11.5 h at 25% |
| Champion 4500-Watt Dual Fuel Inverter Inverter, dual fuel | 3,500 | 4,500 | 2.3 | 14 h at 25% |
| Westinghouse iGen4500 Inverter | 3,900 | 5,000 | 3.4 | 18 h at 25% |
| Honda EU7000iS Inverter | 5,500 | 7,000 | 5.1 | 18 h at 25%; 6 h at full load |
| Westinghouse WGen9500DF Dual fuel | 9,500 | 12,500 | 6.6 | 17.5 h at 25%; 12 h at 50% |
References
- Eugene Water & Electric Board, Generator sizing considerations
- Virginia Tech Extension, Estimating Appliance and Home Electronic Energy Use (Feb 2020)
- ResMed battery guide (AirSense 10 at 10 cm H2O, 12 V)
- ResMed AirSense 11 user guide (peak power 73.2 W)
- Philips EverFlo brochure (average power 350 W)
- Icom IC-7300 specifications
- Yaesu FT-891 specifications
- Yaesu FT-991A specifications
- Xiegu G90 operation manual
- Icom IC-705 specifications
- Kenwood TM-V71A specifications
- Icom IC-2730A specifications
- Yaesu FTM-6000R operating manual
- Yaesu FT-65R operating manual (SBR-25LI 7.4 V, 1,950 mAh)
- Baofeng UV-5R battery (7.4 V, 1,800 mAh)
- Rocky Talkie 5 Watt Radio battery (7.4 V, 1,800 mAh)
- Rocky Talkie Mountain Radio battery (1,550 mAh)
- CDC: Use a generator safely
- NREL solar resource maps (peak sun hours)
Numbers marked as estimates are ours where the maker does not publish a figure. If you find an official number, tell us and we will update it.